JTEKT TOYOPUC Performance
TOYOPUC-PC10 series Ethernet connection
Add array OPCItems as Advise from a OPC Client.
It is measured reading time from added OPCItems. Communication performance is defined as average time of ten times measurement.
This time means to read the value of a continuous area of the device.
PC specification
Genuine Intel(R) CPU T250 2.00GHz
Windows XP Professional / SP2
DeviceXPlorer OPC Server Ver4.0
OPC Client - Visual Basic 6.0
UpdateInterval - 1ms
PLC setting
PC10G
CPU Built-in Ethernet(100BASE-TX)
Max scan time: < 10msec
Communication Performance
(sec)
|
| 1024
| 2048
| 4096
| 8192
| 16K
| 32K
| 64K
| 128K
|
| Average
| 0.054 |
0.105 |
0.231 |
0.421 |
0.863 |
1.455 |
2.713 |
5.313 |
| Max
| 0.056 |
0.112 |
0.222 |
0.434 |
0.881 |
1.475 |
2.747 |
5.378 |
| Min
| 0.050 |
0.103 |
0.203 |
0.400 |
0.841 |
1.422 |
2.666 |
5.250 |
Results
In case of continuous Data register(D), it is possible to get max 20,000 points per sec.
Comment
*Graph displays average time of fifty times measurement.(1point = 1word)
*In case of 32K points access , Read 32K points by using 2 devices.( 16K point per 1 device).
*The result only means our examination, it doesn't guarantee performance.