SIEMENS SIMATIC Performance
SIMATIC-S7 series Ethernet connection
Add array OPCItems as Advise from a OPC Client.
It is measured reading time from added OPCItems. Communication performance is defined as average time of ten times measurement.
This time means to read the value of a continuous area of the device.
PC specification
OS:
    Windows 7 Professional  32bit OS
CPU:
    Intel(R) Core(TM) i7 CPU 860 @2.80GHz
Memory:3.00GB
OPC Server:
    DeviceXPlorer OPC Server Ver4.2.0.2
OPC Client:
    OPCClient sample VcSampleOpc(C++)
Cable:
    100BASE-TX cross cable connecting directly
OPC Server setting
Protocol Timer Tick:10msec
Timer Tick for Async Update Mode:10msec
Multi Access Mode:Enable
Multi Access for Snyc Asnyc:Disabled
Async Update Mode:Disabled
PLC setting
CPU:CPU315
Communication unit:CP343
Register:DB1:0-DB1:8191,DB2:0-DB2:8191,DB3:0-DB3:8191,DB4:0-DB4:8191
Max scan time:1msec
Communication Performance
≪CP343≫
(sec)
|
| 1024
| 2048
| 4096
| 8192
| 16K
| 32K
|
| Average
| 0.182 |
0.368 |
0.724 |
1.427 |
2.843 |
5.703 |
| Max
| 0.190 |
0.380 |
0.765 |
1.461 |
2.882 |
5.733 |
| Min
| 0.172 |
0.360 |
0.700 |
1.412 |
2.811 |
5.653 |
≪Built-in Ethernet≫
(sec)
|
| 1024
| 2048
| 4096
| 8192
| 16K
| 32K
|
| Average
| 0.050 |
0.100 |
0.190 |
0.370 |
0.742 |
1.486 |
| Max
| 0.050 |
0.101 |
0.191 |
0.370 |
0.743 |
1.489 |
| Min
| 0.050 |
0.100 |
0.190 |
0.370 |
0.741 |
1.477 |
Results
In case of Ethernet unit, to access continuous Data Block(DB), it is possible to get max 6,000 points per sec.
In case of Built-in Ethernet, to access continuous Data Block(DB), it is possible to get max 20,000 points per sec.
CPU Built-in Ethernet is about three times as earlier as the Ethernet unit.
Commnet
*Graph displays average time of ten times measurement.(1point = 1byte)
*The result only means our examination, it doesn't guarantee performance.
[Jun 2010]
Interface performance
Results of measurement of each interface(eg.sync /async /datachange event etc).
(detail)