SHARP SATELLITE Performance
JW series Ethernet communication
Add array OPCItems as Advise from a OPC Client.
It is measured reading time from added OPCItems. Communication performance is defined as average time of ten times measurement.
This time means to read the value of a continuous area of the device.
PC specification
OS:
    Windows 7 Professional  32bit OS
CPU:
    Intel(R) Core(TM) i7 CPU 860 @2.80GHz
Memory:3.00GB
OPC Server:
    DeviceXPlorer OPC Server Ver4.2.0.2
OPC Client:
    OPCClient sample VcSampleOpc(C++)
Cable:
    100BASE-TX cross cable connecting directly
OPC Server setting
Protocol Timer Tick:10msec
Timer Tick for Async Update Mode:10msec
Multi Access Mode:Enable
Multi Access for Snyc Asnyc:Disabled
Async Update Mode:Disabled
PLC setting
CPU:JW-321CU
Communication unit:JW-25TCM
Register:D009000-D79777,D109000-D179777(total 16k)
Max scan time:7msec
Communication Performance
(sec)
|
| 1024
| 2048
| 4096
| 8192
| 16K
| 32K
| 64K
| 128K
|
| Average
| 0.031 |
0.118 |
0.124 |
0.249 |
0.497 |
1.011 |
2.041 |
4.097 |
| Max
| 0.031 |
0.620 |
0.124 |
0.249 |
0.499 |
1.014 |
2.044 |
4.103 |
| Min
| 0.031 |
0.062 |
0.124 |
0.249 |
0.483 |
0.999 |
2.028 |
4.072 |
Results
In case of continuous D register, it is possible to get max 32,000 points per sec.
Comment
*Graph displays average time of ten times measurement.(1point = 1word)
*In case of 32K points access , Read 32K points by using 2 devices.( 16K point per 1 device).
*The result only means our examination, it doesn't guarantee performance.
[Jun 2010]