SITEMAP   PRIVACY   JAPANESE
FAWEB
  JAPAN   HOME  |  Product  |  Support  |  Knowledge  |  Download  |  Sales  |  Company  |  Contact
OPC Server

OPC Server
Top Page
Feature
Datasheet
Support PLC
Introduction
Release Note
SCADA List
Sales Partners
FAQ
Price
Ability
Sample
   MELSEC-Q
   MELSEC-QnA
   MELSEC-A
   Visual Basic 6.0
   Visual Basic .NET
   EXCEL
Tips
SCADA Setting
Manual/Demo

OnlineShop

OPC-F Member
You are Here : HOME > Product > OPC Server > MELSEC-Q Series Ethernet Parameter BACK

opc


MELSEC-Q Series Ethernet Parameter


When Ethernet is used, it explains the parameter setting needed on the PLC side.
The MELSEC-Q series can set the Ethernet parameter of IP address/port number etc. on the setting of the parameter of GX Developer screen.

The sample explains here assumes the case to set as follows on the OPC Server side.
This sample project can be downloaded here.

Host IP Address 192.168.0.1
Host Port Number 0 / 1027 (TCP Fullpassive)
MELSEC IP Address 192.168.0.4
MELSEC Port Number 1025


Network Parameter
Parameter

Open GX Developer's "Network Param" page, specify "Ethernet" for "Network Type," and enter the network number, group number, and station number. When QJ71E71 is installed in slot 0 (side of CPU), head I/O No:"0" and network No are set, and "1" and group No are set in "0" and the exchange number is set to "1".


Network Parameters - Operations
Operations

Set "Communication Data Code" to "Binary code," and "Initial Timing" to "Always wait for OPEN." Check "Enable Write at RUN time," and enter the IP address of the PLC in decimal value. When using TCP/IP, you should select "KeepAlive" in "TCP Existing Confirmation Setting".

- If you do not check "Enable Write at RUN time," you cannot write to the PLC from I/O Server.
- "TCP Existing Control" is displayed with GX Developer after version 8.05F .
- KeepAlive function is valid for Ethernet Unit version, after upper 5 place of serial number is '05051'.


Network Parameters - Initial Setting
Initial

When using TCP/IP, configure the existence confirmation parameters appropriately. When the existence confirmation parameters are not configured appropriately, re-establishing connection after a network error may be difficult or impossible. In the above example, existence confirmation is done three times every 5 seconds starting 10 seconds after the communication stops.

- Please note that it is for ten minutes after it is cut the possibility not to be able to be reconnected because the default value is confirmation ..unsealing.. Hageme ten minutes later the connection.
- Please set the existence confirmation parameters appropriately when you use TCP/IP. It is reconnected and note it, please. When the network trouble of the cable determination etc. when it is improper occurs, the existence confirmation parameters takes time to be reconnected.


Network Parameters - Open Setting
Open

Configure the ports you wish to open. In the above-mentioned setting example, UDP/IP, port 2, and port 3 are defined as TCP/IP with port 1.

- Configuration of this page is not required when you wish to use automatic open UDP port (default 5000) only.
- For open setting, "Fixed Buffer Communication Procedure" must be set to "Procedure Exists." - "Local Port Number" and "Destination Port Number" must be entered in hexadecimal. - When using UDP, broadcast becomes available by setting the "Destination IP Address" to "255.255.255.255" and "Destination Port Number" to "FFFF."

BACK

Copyright © 1998-2006 TAKEBISHI Corporation All rights reserved.

FAWEB.NET
TAKEBISHI Corporation
29 Mamedacho Nishikyogoku Ukyoku Kyoto 615-8501, JAPAN
TEL: +81-75-325-2171 / FAX: +81-75-325-2273 fa-support@takebishi.co.jp